Approvals & Certifications
- ATEX
- CCOE
- CE
- CSA Explosion-proof
- FM - Flameproof. Class I, Div. 1, Groups B, C, D, Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C), Class I, Zone 1, AEx d IIB + H₂, Typical 4/IP55
- IEC
- INMETRO
- RosTech, FSTS
Cover - for Local Enclosure
- Blind Cover - Flameproof
- Glass Lens Cover - Flameproof
Electronics - Standard Features
- Continuous Diagnostics Detect Sensor Fault
- Detects Min. Flow or Presence / Absence of Flow
- Easy / Fast Calibration
- Excellent Low Flow Sensitivity
- Hygienic Design Available
- Non-Linear mA Output Signal Can be used for Trending, Diagnostics & Repeatable Flow/level Indication
- Temperature Compensation
Enclosure, Body Material
- 304 Stainless Steel
- 316 Stainless Steel
- Cast Aluminum A356 Containing less than 0.2 % Copper
Flange Material
- 316 Stainless Steel
- 316L Stainless Steel
- Hastelloy C
- Monel
Input Power
- 19.2-28.8 Vdc 50/60 Hz
- Power Consumption: 3.5 W at 24 Vdc
- Power Consumption: 4.5 W at 30 Vdc
Insertion 'U' Length
- Custom 'U' Lengths: 2” to 130” (5 cm to 330 cm) in 1” (2.5 cm) Increments
Operating Pressure - Sensor
Operating Temperature - Electronics
- -40° to 70° C (-40° to 158° F)
Operating Temperature - Sensor
- -73° to 454° C (-100° to 850° F)
- Extended Range: -73° to 454° C (-100° to 850° F)
Options
- LED Indication of Flow/Level
- Remote
Response Time
- 1 to 10 seconds (Typical - Dependant Upon Sensor Type, Application, & Set Point Adjustment)
Switch Point Range
- Air: 0.1 to 500 FPS (0.03 to 150 mps)
- Water: 0.01 to 5.0 FPS (0.003 to 1.5 mps) (spherical Tip & Twin Tip Sensors)
Switch Type
- DPDT Switch: 8 Amp at 120 Vac, 250 Vac / 8 Amp at 30 Vdc, 0.5 Amp at 125 Vdc / Hermetically Sealed 1 Amp at 28 Vdc, 0.5 Amp at 125 Vdc
Wetted Materials
- 316, 316L Stainless Steel
- Hastelloy C
- Monel