Description
The Rosemount 3144P Temperature Transmitter provides industry-leading accuracy, stability and reliability for your temperature measurements.
It features a dual-compartment housing to ensure reliability and advanced diagnostics to keep your measurement point up and running.
When combined with Rosemount X-well™ Technology and the Rosemount 0085 Pipe Clamp sensor, this transmitter can provide accurate measurement of process temperature, eliminating the need for a thermowell or process penetration.
Features- Industry-leading accuracy and reliability for best performance in critical control and safety applications
- Transmitter-sensor matching improves measurement accuracy up to 75%
- 5-year long-term stability extends calibration intervals to reduce trips to the field
- Rosemount X-well Technology measures temperature without a process penetration for reduced design, installation and maintenance costs
- Dual compartment housing provides superior protection in harsh environments
- Hot Backup™ capability and sensor drift alert utilizing dual sensors ensure measurement integrity
- Thermocouple degradation diagnostic monitors thermocouple health to detect degradation before failure
- Minimum and maximum temperature tracking allows monitoring of temperature extremes for easy troubleshooting
- Transmitter supports multiple protocols for integration in many host environments across many industries
- Device dashboards provide easy interface for simplified device configuration and diagnostic troubleshooting
Configure
Specifications
Specifications
Brand
Accuracy
- ± 0.02 % of Span
Alarm
- NAMUR Alarm & Saturation Signal Levels
Ambient Temperature Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- ATEX
- CSA
- FM
- IEC 61508 (SIL)
- IEC Ex
- INMETRO
- NEPSI
- TIIS
Conduit Connection
- A Size Mini, 4-Pin Male Connector (minifast)
- M12, 4-Pin, Male Connector (eurofast)
Configuration
- FOUNDATION Fieldbus Protocols
- HART Protocols
Damping Adjustment
- 0 seconds Default
Display
- LCD Display
Electrical Connectors
- 1/2” NPT
- JIS G 1/2”
- M20 x 1.5
- PG13.5
Electromagnetic Interference Effect
- Meets or Exceeds All Requirements Listed Under IEC 61326: 2006.
Enclosure Finish
- Polyurethane Paint
Enclosure, Body Material
- 316 Stainless Steel
- Aluminum
Environmental Protection
- IP66
- IP68
- NEMA 4X / IP66, 68
Humidity
- 0 to 99 % Relative Humidity
Input Power
- 12.0-42.4 Vdc
Mounting
- “L” Mounting Bracket for 2-inch Pipe or Panel Mounting
- “U” Mounting Bracket for 2-inch Pipe Mounting
O-Ring Material
- Buna-N
Operating Temperature
- -40° to 85° C (-40° to 185° F)
Output
- 2-Wire 4-20 mA
Power Supply Effect
- ± 0.005 % of Span Per Volt
Process Temperature
- 55° to 450° C (131° to 842° F)
Sensor, Probe Connection
- 2-Wire
- 3-Wire
- 4-Wire
- Backup
- T/C & mV
Sensor, Probe Type
- B Thermocouple
- DIN Typical L
- DIN Typical U
- E Thermocouple
- GOST L
- J Thermocouple
- K Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- Typical W5Re/W26Re
Storage Temperature
- -50° to 120° C (-58° to 248° F)
Temperature Effect
- 0.001 % of Span