Description
The LS6000 is an economical, basic feature point level switch that can sense a wide range of liquid and dry materials. Its robust design and durable Delrin insulator make this unit well suited for use in dry materials, such as powders, sand, aggregate, grain or other bulk solids.
Unlike rotating paddles, vibrating forks or other mechanical instruments, the LS6000 level switch has no moving parts. There are no motors to burn up, bearings to wear out or parts to jam.
Proprietary radio frequency (RF) technology provides excellent level measurement and stability while having the ability to ignore significant product buildup, thus eliminating the need for recalibration.
Features- Ignores significant product build up
- Solid state, no moving parts
- Simple installation and calibration
- Explosion proof housing standard
- Probe length easily field modified
- Rugged construction handles roughest products
Configure
Specifications
Specifications
Power
- 115 Vac (± 15 %) 50/60 Hz, 2 Watts Standard
- 12 Vdc, 24 Vdc or 230 Vac Optional
Output
- 2 Form C Contact DPDT Relay
- 5 A Resistive at 125, 230 Vac; 30 Vdc
On Board Fuse
- 250 mA
Failsafe
- Selectable High or Low Level
RF Frequency
- Approx. 1.3 MHz
Temperature Range
- Delrin Insulator: -30° to 250° F
- Teflon Insulator: -30° to 450° Optional
Pressure
- 1,500 psi @ 75° F - 1” NPT Standard
- 300 psi @ 75° F - 3/4” NPT Optional
Enclosure
- Cast Aluminum, Explosion Proof - Class I, Groups C & D; Class II, Groups E, F & G
Applications
Applications
- High or Low Level Alarms
- Sump Control
- Oil/Water Interface Detection
- Dry Pump Protection
Liquids & Dry Solids
- Water/Wastewater
- Acids/Caustics
- Chemicals/Oils
- Slurries
- Flour/Grains
- Powders
- Plastics
- Sand/Cement
- Wood Chips